Gas Target: Difference between revisions

From DRAGON Wiki
Jump to navigation Jump to search
Line 44: Line 44:


=== Normal operation ===
=== Normal operation ===
When the zeolite cleaning trap is in operation, there is a large inventory of "invisible" hydrogen adsorbed on the zeolite molecular sieve. For a trap inlet pressure (CMTRIN) of 45 Torr the adsorbed hydrogen amounts to 5 litres at STP, while the "free" recirculating hydrogen may be only 15% of this amount. The heat of combustion of this total amount of hydrogen is approximately 50 kJ - enough to raise 5 tonnes a height of 1 m.


=== Unattended gas target, trap containing absorbed hydrogen  ===
'''IT IS ESSENTIAL THAT THE TARGET OPERATOR KNOWS WHETHER THE TRAP IS COLD AND WHETHER IT IS "LOADED" WITH HYDROGEN.'''


== Protection of equipment  ==
The correct response to the sonalert alarm from the LN2 automatic filler or from the EPICS system depends upon this knowledge. Therefore:


== General description of the gas target system ==
'''ANY SIGNIFICANT CHANGE IN THE INVENTORY OF HYDROGEN IN THE CLEANING TRAP MUST BE ACCOMPANIED BY AN ENTRY IN THE DRAGON “Equipment Status” elog (https://elog.triumf.ca/Dragon/}<nowiki/>.'''


=== Gas supply shack ===
The entry should indicate trap status (warm/cold), estimated hydrogen inventory.. The 6-litre Buffer Tank should be used to control the amount of gas loaded into the trap. The number of 50-Torr "loads" from the Inlet Buffer Tank should be tallied during an initial fill of the trap. Any large deviation from the expected 15-20 "loads" to reach approx. 45 Torr pressure must be investigated and the problem fixed.


=== Windowless gas target ===
(During tuning for a new beam energy it is common for ISAC Operations to request that gas be removed from the DRAGON target. Each time that this is done, some of the "free" circulating hydrogen is lost. It is convenient to replenish the supply by adding 1 or 2 "loads" of gas through the Inlet Buffer Tank when the target cell is again filled with recirculating gas. This is considered a routine operation which need not be reported in the Equipment Status elog)


== Operating the target ==
The purpose of the cleaning trap is to remove air and other impurities from the recirculating hydrogen gas. Thus, when the trap does its job it is almost impossible to detect any small leak of air into the target system. The implications for target operation with a trap are:


=== Pre-run checks ===
* A cold trap which has been loaded with hydrogen should be treated as though it contains air also, in a potentially explosive mixture. An exhaust fan must be running whenever a cold trap contains hydrogen, to allow safe dilution of hydrogen in the event of an unanticipated release from the trap through the pressure relief valve. Normal procedure when the trap is being warmed up is to pump on it with the roughing pump, which vents to the high-air-flow exhaust line.
* Before cooling the trap, it must be checked that any air leaks are less than could amount to 1.5 atm-litre over a 2-week period (assuming a trap will be kept cold no longer than 2 weeks at a time). Possible sources include leaks in the differential pumping stages, in the trap itself or in the buffer tank and gas supply lines. The leak rates should be measured by pumping down the system, then isolating it with the Roots blowers continuing to run; the gauge CMTRIN connects to an effective volume of 12 litres, from which the quantity of gas (leaking or outgassing) may be calculated using an observed rate of increase in CMTRIN. Other sources are HEBT or the DRAGON separator when isolation valves HEBT2:IV8 or DRA:IV11 are open. At an estimated 1000 litre/sec conductance in the beam pipes, the sum of partial pressures of air upstream and downstream of the target should be less than 1E-6 Torr when there is no gas added to the trap.
* Failure of the automatic LN2 filling system or failure of the primary exhaust fan must trigger immediate action, either to fix the fault or to begin controlled warmup of the trap.


=== Pumping out the target ===


=== Filling the cleaning trap with hydrogen ===
===Unattended gas target, trap containing absorbed hydrogen===


=== Filling the cleaning trap with helium ===
==Protection of equipment==


=== Circulating gas through the target, trap in use ===
==General description of the gas target system==


=== Circulating gas through the target, trap not in use ===
===Gas supply shack===


=== Checks of an operating target ===
===Windowless gas target===


=== Temporary pump-out of the target, trap in use ===
==Operating the target==


=== Emptying target and trap at end of running ===
===Pre-run checks===


=== Venting the target to 1 atmosphere ===
===Pumping out the target===


=== Hidden valves ===
===Filling the cleaning trap with hydrogen===


=== Leak checking ===
===Filling the cleaning trap with helium===


== Emergency procedures, response to pump trips ==
===Circulating gas through the target, trap in use===


=== Power outage ===
===Circulating gas through the target, trap not in use===


=== Loss of compressed air to valves ===
===Checks of an operating target===


=== Pump trips ===
===Temporary pump-out of the target, trap in use===
 
===Emptying target and trap at end of running===
 
===Venting the target to 1 atmosphere===
 
===Hidden valves===
 
===Leak checking===
 
==Emergency procedures, response to pump trips==
 
===Power outage===
 
===Loss of compressed air to valves===
 
===Pump trips===

Revision as of 14:00, 25 June 2025

Revision history
Version Author Description Date
1.0 D. Hutcheon Initial Document 27 September 2002
1.1 D. Hutcheon Hidden valves,shack 4 April 2007
1.2 D. Hutcheon Leak checking 27 April 2007
1.3 D. Hutcheon Decadal update 22 January 2019
1.4 A. Lennarz Transferred to wiki June 25th, 2025

Safety with hydrogen as the target gas

The following is a brief outline of safety considerations. For more details, consult the DRAGON Safety Report.

The strategy for safe operation with hydrogen gas is:

  • avoid formation of an explosive mixture of air and hydrogen
  • avoid ignition sources at pressures where combustion may take place


Normal operation

When the zeolite cleaning trap is in operation, there is a large inventory of "invisible" hydrogen adsorbed on the zeolite molecular sieve. For a trap inlet pressure (CMTRIN) of 45 Torr the adsorbed hydrogen amounts to 5 litres at STP, while the "free" recirculating hydrogen may be only 15% of this amount. The heat of combustion of this total amount of hydrogen is approximately 50 kJ - enough to raise 5 tonnes a height of 1 m.

IT IS ESSENTIAL THAT THE TARGET OPERATOR KNOWS WHETHER THE TRAP IS COLD AND WHETHER IT IS "LOADED" WITH HYDROGEN.

The correct response to the sonalert alarm from the LN2 automatic filler or from the EPICS system depends upon this knowledge. Therefore:

ANY SIGNIFICANT CHANGE IN THE INVENTORY OF HYDROGEN IN THE CLEANING TRAP MUST BE ACCOMPANIED BY AN ENTRY IN THE DRAGON “Equipment Status” elog (https://elog.triumf.ca/Dragon/}.

The entry should indicate trap status (warm/cold), estimated hydrogen inventory.. The 6-litre Buffer Tank should be used to control the amount of gas loaded into the trap. The number of 50-Torr "loads" from the Inlet Buffer Tank should be tallied during an initial fill of the trap. Any large deviation from the expected 15-20 "loads" to reach approx. 45 Torr pressure must be investigated and the problem fixed.

(During tuning for a new beam energy it is common for ISAC Operations to request that gas be removed from the DRAGON target. Each time that this is done, some of the "free" circulating hydrogen is lost. It is convenient to replenish the supply by adding 1 or 2 "loads" of gas through the Inlet Buffer Tank when the target cell is again filled with recirculating gas. This is considered a routine operation which need not be reported in the Equipment Status elog)

The purpose of the cleaning trap is to remove air and other impurities from the recirculating hydrogen gas. Thus, when the trap does its job it is almost impossible to detect any small leak of air into the target system. The implications for target operation with a trap are:

  • A cold trap which has been loaded with hydrogen should be treated as though it contains air also, in a potentially explosive mixture. An exhaust fan must be running whenever a cold trap contains hydrogen, to allow safe dilution of hydrogen in the event of an unanticipated release from the trap through the pressure relief valve. Normal procedure when the trap is being warmed up is to pump on it with the roughing pump, which vents to the high-air-flow exhaust line.
  • Before cooling the trap, it must be checked that any air leaks are less than could amount to 1.5 atm-litre over a 2-week period (assuming a trap will be kept cold no longer than 2 weeks at a time). Possible sources include leaks in the differential pumping stages, in the trap itself or in the buffer tank and gas supply lines. The leak rates should be measured by pumping down the system, then isolating it with the Roots blowers continuing to run; the gauge CMTRIN connects to an effective volume of 12 litres, from which the quantity of gas (leaking or outgassing) may be calculated using an observed rate of increase in CMTRIN. Other sources are HEBT or the DRAGON separator when isolation valves HEBT2:IV8 or DRA:IV11 are open. At an estimated 1000 litre/sec conductance in the beam pipes, the sum of partial pressures of air upstream and downstream of the target should be less than 1E-6 Torr when there is no gas added to the trap.
  • Failure of the automatic LN2 filling system or failure of the primary exhaust fan must trigger immediate action, either to fix the fault or to begin controlled warmup of the trap.


Unattended gas target, trap containing absorbed hydrogen

Protection of equipment

General description of the gas target system

Gas supply shack

Windowless gas target

Operating the target

Pre-run checks

Pumping out the target

Filling the cleaning trap with hydrogen

Filling the cleaning trap with helium

Circulating gas through the target, trap in use

Circulating gas through the target, trap not in use

Checks of an operating target

Temporary pump-out of the target, trap in use

Emptying target and trap at end of running

Venting the target to 1 atmosphere

Hidden valves

Leak checking

Emergency procedures, response to pump trips

Power outage

Loss of compressed air to valves

Pump trips